General Order 128
 Section III
 Requirements for Supply Systems
 
 
35.1    Identification of Cables
 
Cables operating at a voltage in excess of 750 volts shall be 
permanently and clearly identified by tags or other suitable means to indicate 
their operating voltage and the circuit with which they are normally associated 
at each manhole or other commonly accessible location of the underground system.
   
   EXCEPTION:
   
 This requirement does not apply where there is only one such cable circuit 
and when diagrams supplied to workmen give sufficient identification of such 
cable.