32.4    Grounds and Neutrals.

 

A.    Neutral Conductors.

 

Neutral conductors of supply circuits shall be considered as carrying the same voltage as the current carrying wires.

 

B.    Ground as a Conductor

 

The grounding of the neutral in single phase or polyphase systems is permitted only for the purpose of stabilizing the neutral of the system, and not for use as a return conductor.

 

C.    Independent Grounds

 

Independent grounds or independent ground connections, the resistance of which does not exceed 25 ohms shall be provided for the following:

 

Lightning arresters.

Low voltage power or lighting circuits.

The neutral wire of 4 wire, 3 phase systems where the line voltage exceeds 2500.

Grounded bond wires.

 

Note    This Rule was modified by Supplement 1.  To see the changes made by supplement 1 click here.  This page contains the wording of the rule prior to Supplement 1.