General Order 64-A
Section IV
Strength Requirements For All Classes Of Lines
43.2 Light Loading
This condition shall be considered as existing in all parts of the state where heavy loading does not apply. This loading shall be taken as the resultant of wind pressure and dead weight under the following conditions:
A. Wind
A horizontal wind pressure of 8
pounds per square foot of projected area on cylindrical surfaces, or 13 pounds
per square foot on flat surfaces shall be assumed, except where wind velocities
greater than those specified frequently occur; in which case a 25% increase of
wind pressure shall be assumed. Where
latticed structures are used, the actual exposed area of one lateral face shall
be increased by 50% to allow for pressure on the opposite face, provided this
computation does not indicate a greater pressure than would occur on a solid
structure of the same outside dimensions, under which conditions the latter
shall be taken.
B.
Ice
A radiall thickness of one–half
inches of ice, weighing 57 pounds per cubic foot, on all conductors shall be
assumed in computing vertical and wind loadings.
C.
Temperature
This shall be considered at the
time of maximum loading to be 0° F. The
normal temperature for computing erection conditions is 60° F. Maximum
temperature (in computing sag under this condition) shall be assumed as 130° F.