General Order 64-A
Section IV
Strength Requirements For All Classes Of Lines
49.5 Insulators
A.
Line
Insulators, supports, clamps and
other miscellaneous attachments shall be designed to withstand with at least
the safety factors, the mechanical stress to which they are subjected by
conductors, wires or structures, under the loading conditions as specified in
Rule 43. Pin insulators shall
effectively engage the thread of the pin for at least two and one-half turns.
B.
Guy
Guy insulators, including
insulators in messengers, shall have mechanical strength at least equal to that
required of the guy wires in which they are installed.
C. Replacements (see Rule 44.2)