General Order 64-A
Section V
Detailed Construction Requirements For Supply Lines
(Class H, L and T Circuits)
54.9 Miscellaneous
A.
Open Wire Drops.
Open wire drops from the line
conductor to another level on the pole or structure shall not impair the
climbing space, nor shall they pass between the conductors of any other
circuits other than the pole conductors, nor shall they clear the conductors of
other circuits by a distance of less than 12 inches under the most severe
conditions. It is recommended that
wherever practicable the lead wires from the line conductors to the other level
be carried in conduit attached to the pole and properly protected, as specified
in Rule 54.6-A1. Where the distance
between levels is in excess of 10 feet, additional supports shall be installed
equidistant from the levels involved.
B. Low Voltage Racks.
(1) General: Conductors of 0-750 volts which are of the same material throughout and have the equivalent of a double braid weatherproof covering may be attached to one side of pole sin spans not exceeding 250 feet in light loading districts.
(2) Vertical Separation and Span Lengths: A minimum vertical separation of 6 feet shall be maintained between the top conductor supported by the rack and conductors of more than 750 volts carried above it on the pole, or a guard arm shall be installed directly above the rack and parallel to the conductors, in which case the minimum vertical clearance below conductors of more than 750 volts may be reduced to 4 feet. The vertical separation of conductors carried on the rack shall be not less than 4, 8, or 12 inches for spans of 150, 200 and 250 feet, respectively.
(3) Conductor Clearance From Surface of Pole: The conductors shall maintain a clearance of not less than 3 inches from the surface of poles.
(4)
Climbing Space: The 15
inch center line of pole clearance specified in Table 1, Case 7, need not
apply, provided that the full climbing space is maintained past the rack for a
distance of 4 feet above and 4 feet below the top and bottom conductors,
respectively, supported thereon.
Lateral runs and service drops may be taken from the main rack run and
supported by a rack installed on the side of the pole opposite the main
rack. Such lateral runs and service
drops shall not be permitted to obstruct the climbing space when installed on
the opposite side of the pole from the main rack conductors they shall form an
angle of departure of not less than 30° from the main rack conductor, which for
the purpose of measuring the angle of departure is considered as being on the
same side of the pole as the lateral runs and service drops in question. No limit is placed on the angle between the
service drop and the main rack run where such service drop is taken from the
main rack. To facilitate the climbing
space requirement it is recommended that racks be put on the sidewalk side of
pole. (See App. G, Fig. 89.)