General Order 64-A
Section VII
Detailed Construction Requirements For Trolley Lines
(Class T Circuits)
74.3 Material and Strength (See Sec. IV, Rule 49.4)
In determining strength
requirements, Class T lines are classed as ordinary supply lines of equal
voltage and will take grades of construction accordingly. This will generally mean Grade “C”
construction for D.C. trolley lines of 0-750 volts, Grade “A” or “B” being
required at crossings over railways according to the importance of the railway
crossed.
The minimum size which shall be
used for trolley contact conductors on public streets or highways is No. 0
solid copper, or other wire of equal strength.
The minimum size of wire to be
used as a feeder span or feeder auxiliary span wire shall be No. 4/0 stranded
copper. Other Class T conductors shall
comply with Rule 49.4 and 54.