86.2
Use.
Where mechanical loads imposed on
poles, towers or structures are greater than can be safely supported,
additional strength shall be provided by the use of guys or other suitable
construction. Where necessary, guys
shall be used wherever conductor stresses are unbalanced, as at dead ends or
angles.
Where guys are used with poles or
similar structures capable of considerable deflection before failure, they
shall be able to support the entire stress, the pole below the point of guy
attachment acting merely as a strut.
Guys shall be attached to
structures as nearly as possible at the center of load. They shall be maintained taut and such
strength as to meet the safety factors of Rule 44.