General Order 64-A
Section IX
Joint Poles Or Poles Jointly Used
92.1 Clearances.
A.
From Center Line of Poles.
Where conductors are supported on
crossarms on jointly used poles, a minimum horizontal clearance of 15 inches
shall be maintained. (See Table 1, Case
7.)
Supply cables as treated in Rule 57.8 and communication cables may be attached directly to one side of jointly
used poles.
B.
Rack Construction.
Where rack construction is used
on jointly used poles, the following minimum vertical clearances shall apply:
Racks Above |
|
Conductors or cables on Cross arms |
4 feet |
Unguarded cables or racks attached to pole |
6 feet |
Guarded cables or racks attached to pole |
4 feet |
Unguarded racks below. |
|
All Circuits |
4 feet |
Guarded racks below all circuits |
|
All Circuits |
4 feet |
C.
Cable Construction. (See App. G, Fig. 89.)
Where cables are attached
directly to jointly used poles the following minimum vertical clearances
between such cables and cables or conductors of other classifications shall
apply:
Cables above |
|
Conductors or cables on cross arms |
4 feet |
Unguarded racks attached to pole |
6 feet |
Unguarded cables attached to pole |
4 feet |
Guarded cables or racks attached to pole |
4 feet |
Unguarded cables below |
|
All open wire circuits |
6 feet |
All grounded cables |
4 feet |
Guarded cables below |
|
Circuits more than 7500 volts |
6 feet |
All other circuits |
4 feet |
D.
Paired Conductors.
One Paired Communication
Conductor may be carried on brackets on poles which support supply conductors,
provided the poles are set on private property and a minimum vertical
separation of 5 feet is maintained and both classifications of circuits are
used for service to the same party.
Paired wire line extensions from
cable terminals may be temporarily attached directly to poles by means of brackets
at a distance not less than 5 feet below supply conductors of 0-750 volts,
without guard arm, leaving one side of poles free for climbing. Such attachment may have also be made not
less than 48 inches above supply conductors of 0-750 volts. (See App. G, Fig. 88.)
E.
From Non-Energized Equipment.
The 4 foot vertical minimum
separation with guard arm, between supply and communication conductors, may be
reduced to 40 inches with guard arm where applied to separation between
conductors of 0-750 volts of one classification and normally non-energized
equipment of the other classification provided the latter is not installed
within the climbing space.
F.
Police And Fire Alarm Circuits.
Police and fire alarm circuits
which are permitted to occupy the position between supply circuits of 0-750
volts (rack construction excepted) and other communication circuits with a
minimum vertical clearance of 2 feet from each of such circuits provided the
conductors of such police and fire alarm circuits are protected with a covering
equal to double braid weatherproofing and are carried at a minimum horizontal
distance of 25 inches from the center line of the supporting pole. This does not prohibit the carrying of these
conductors at this location in messenger ring construction, provided the
messenger is insulated in accordance with guy requirements and no part of the
messenger is grounded throughout its length.
G.
From Span Wires of Class T Circuits.
Span wires and conductors
(including cables) shall maintain the clearances specified in Table 2, Case 8
to 13, inclusive, where the span sire insulation can not be maintained due to
climatic or other conditions.
H.
From Drip Loops.
The lowest point of the drip loop
from the terminal or end of a conduit run shall a minimum vertical separation
of one foot from the nearest supply conductor level below it.
I.
From Cable Terminals or Boxes.
A metal communication terminal or
box shall not be placed less than 6 feet vertically below supply conductors,
excepting that if a suitable guard arm is placed over the box or terminal the
clearance may be reduced to 4 feet.
It is recommended that where the
communication conductors are in cable attached directly to one side of the
pole, the terminal or box be placed below the cable arm or cable guard arm.
J.
From Street Lighting Equipment.
Street lighting equipment,
including the supporting rods, braces and guys, shall not be less than one foot
above or below all conductors of open wire and not less than one foot above or
two feet below all circuits carried in cables.
K.
From Transformers on Platforms.
Where transformers are installed
on racks having a continuous flooring that affords adequate protection to
equipment below, cables may be installed at a minimum vertical distance of 12
inches below transformer cases provided the specified ground clearance
requirements are maintained.