General Order 64-A
Section X
Supply And Communication Lines In Crossings Or Conflicts
102.1 Duplex Pin Construction.
Where this type of construction
is used in crossings, a guard arm of at least the length of the longest duplex
arm shall be placed not less than 6 inches below the lowest duplex arm except
where an arm supporting other than duplex construction is used in lieu thereof.
In addition, the corresponding ends of all
duplex arms and the guard arm shall be so connected as to further prevent any
of the conductors from falling into the crossing.