General Order 64-A
Appendix
B
Mechanical And Loading Data For Conductors
TABLE 24 MINIMUM SAGS FOR COMMUNICATION CONDUCTORS IN GRADE “F” CONSTRUCTION |
||||||||||||
Conductors |
|
|
||||||||||
Loading |
Light Loading District |
Heavy Loading District |
Light Loading District |
Heavy Loading District |
||||||||
Temperature (F) |
25° |
60° |
100° |
0° |
60° |
80° |
25° |
60° |
100° |
0° |
60° |
80° |
Span –100 feet |
3 |
4 |
6 |
3 |
6 |
7 |
4 |
6 |
9 |
3 |
7 |
8 |
Span –125 feet |
4 |
6 |
9 |
5 |
9 |
11 |
7 |
9 |
14 |
5 |
11 |
13 |
Span –150 feet |
6 |
10 |
14 |
7 |
13 |
16 |
10 |
12 |
20 |
8 |
16 |
19 |
Span –175 feet |
10 |
13 |
18 |
10 |
18 |
22 |
12 |
16 |
26 |
--- |
--- |
--- |
Span –200 feet |
13 |
17 |
24 |
13 |
23 |
29 |
14 |
20 |
32 |
--- |
--- |
--- |
Span –225 feet |
16 |
21 |
30 |
--- |
--- |
--- |
19 |
24 |
39 |
--- |
--- |
--- |
Span –250 feet |
20 |
26 |
37 |
--- |
--- |
--- |
23 |
34 |
51 |
--- |
--- |
--- |