General Order 64-A
Supplement Number 1
Original Version
Rule 52.4-D
52.4-D. New Rule
Strikeout and Underlined Version
Rule 52.4-D
52.4-D.
Designation
Of Common Neutral.
In common primary and secondary
grounded neutral systems, where the common neutral line conductor is installed
in a primary pin position, it shall be designated by an approved noncorrosive
metal tag having a minimum diameter of not less than one inch upon which shall
be permanently imprinted o letters "CN" not less than five-sixteenths
(5/16) inch in height. Said tag shall be attached securely to and maintained on
the common neutral conductor at each pin position of line arm and buck arm at a
distance not more than twelve (12) inches from the face of the cross arm on the
climbing side of each pole and so installed as to be clearly visible at all
times.
Final Version
Rule 52.4-D
52.4-D.
Designation
Of Common Neutral.
In common primary and secondary
grounded neutral systems, where the common neutral line conductor is installed
in a primary pin position, it shall be designated by an approved noncorrosive
metal tag having a minimum diameter of not less than one inch upon which shall
be permanently imprinted o letters "CN" not less than five-sixteenths
(5/16) inch in height. Said tag shall be attached securely to and maintained on
the common neutral conductor at each pin position of line arm and buck arm at a
distance not more than twelve (12) inches from the face of the cross arm on the
climbing side of each pole and so installed as to be clearly visible at all
times.