36.3 Neutral Conductors
A.
Material
Neutral conductors
shall be of copper or other corrosion-resistant material if bare, and may be of
aluminum or other material if suitably protected from corrosion.
B.
Size
Neutral
conductors shall be of the size required to carry the estimated current to
which they may be subjected. As a minimum they shall have a cross sectional
area of approximately 50 percent or more of the area of the largest related
phase conductor, if of the same material. If the neutral conductor is of
material having different conductivity from the phase conductors, such 50
percent requirement shall be adjusted upwards or downwards inversely as the
ratio of the conductivities of each material. In no case shall neutral
conductors be smaller than the equivalent of No.6 A WG Copper.