Original
General Order
95
 
Section
IV
 
Strength Requirements for All Classes of
Lines
 
Table 3
 
Class of Circuits involved at upper level |
Other facilities at lower level at crossing, conflicts or on poles jointly used |
Grade of construction to be used at upper level |
H |
Major Class C Circuits |
“A” |
H or L |
Major railways (steam, electric or other motive power at crossing only) |
“A” |
H or L |
Minor railways (at crossing only) |
“B” |
H |
Under all conditions not required to be grade “A” except supply cables treated as specified in Rule 57.8 |
“B” |
L |
Under all conditions not required to be Grade “A” or “B” |
“C” |
Supply cables treated as specified in Rule 57.8 |
Under all conditions |
“C” |
Major Class C |
Class H circuits |
“A” |
Minor Class C |
Class H circuits |
“B” |
C- |
Major railways (at crossing only) - |
“B” |
C |
Class L circuits of more than 750 volts |
“C” |
C |
Supply cables treated as specified in Rule 57.8 |
“F” |
C |
Under all conditions not required to Grade “A,” “B,” or “C” |
“F” |
 
Note: Rule 57.8 specifies bonding and grounding of sheath and messenger of supply cables.