63.3 Guys and Anchors
A. Guys
Guys shall be galvanized steel strand not less than 5/16 inch in diameter, or other corrosion resistant material of equal tensile strength, or they shall be rolled rods of galvanized steel or other corrosion resistant material, with a tensile strength at least equivalent to 5/16-inch steel cable.
B. Anchors
Anchor rods shall be galvanized steel not less than 5/8 inch in diameter or shall be of other material of equal strength and durability.