78.2    Private Communication Conductors

 

The general requirements for private communication conductors of trolley line systems are specified in Rules 20.5-B, 32.4-C and 89 of Section VIII.  In addition to the treatment therein provided, private communication wires (Class C) owned by and used solely in the operation of trolley systems may, where suitably insulated, be attached to span wires supporting trolley contact conductors of such systems when installed and maintained in accordance with the following provisions.

 

A.    Attached to Unenergized Span Wires

 

Private communication conductors (Class C) may be supported by unenergized portions of span wires provided they are attached between the first span wire insulator specified in Rules 77.6-A1 and 77.6-A2 or the second span wire insulator specified in Rule 77.6-A4 and the pole or structure.  They shall not be attached to the section of span wire between contact conductor hangers except within such section of span wire sectionalized by means of insulators placed between 4 feet and 5 feet from each contact conductor hanger.

 

B.    Attached to Energized Span Wires

 

Private communication conductors (Class C) may, where necessary, be supported by feeder cables of 0-750 volts used as span wires when such communication conductor attachments to feeder spans are insulated for not less than the trolley voltage.