Original General Order 95
Section X
Supply and Communication Lines in Line
Crossings or Conflicts
103.5 Crossing or Colinear Clearances
Where supply conductors of 750-7500 volts cross over, or are above and in conflict, or above and colinear with communication conductors within 6 feet radially of a pole or structure which supports the communication conductors, the vertical clearance specified in Table 2, Case 3, Column E and Case 5, Column C (48 inches) shall be increased to not less than 60 inches.