GO 128, Rule 34.3-B

 

34.3-B    Guarding Live Parts

Compartments and enclosures which will, during normal operation, contain exposed live parts shall be designed and installed to prevent a person from passing a wire or other conducting material into such compartment from the outside when it is closed. This requirement is not intended to prevent normal work operations such as fishing ducts and installing cable.

 

Strikeout and Underline Version

GO 128, Rule 34.3-B

 

34.3-B    Guarding Live Parts

 

Compartments and enclosures which will, during normal operation, contain exposed live parts shall be designed and installed to prevent a person from passing a wire or other conducting material into such compartment from the outside when it is closed. This requirement is not intended to prevent normal work operations such as fishing ducts and installing cable.

 

EXCEPTION:

 

Pad-mounted equipment that contains exposed live parts shall be installed to resist the passing of a wire the equivalent of a bare number 18 AWG from the outside between the pad and the housing of the equipment, into the compartment which contains live parts when it is closed.

 

 

Final Version

GO 128, Rule 34.3-B

 

 

34.3-B    Guarding Live Parts

 

Compartments and enclosures which will, during normal operation, contain exposed live parts shall be designed and installed to prevent a person from passing a wire or other conducting material into such compartment from the outside when it is closed. This requirement is not intended to prevent normal work operations such as fishing ducts and installing cable.

 

EXCEPTION:

 

Pad-mounted equipment that contains exposed live parts shall be installed to resist the passing of a wire the equivalent of a bare number 18 AWG from the outside between the pad and the housing of the equipment, into the compartment which contains live parts when it is closed.