Original Version
Rule 58.1-B3
58.1-B3)
From Hardware: Equipment cases, hangers, and other
metal parts in contact therewith shall clear through bolts, arm braces of metal,
and other hardware elements, by not less than 1.5 inches; except that such cases
and hangers shall clear crossarm braces and crossarm through bolts by not less
than 1 inch air–gap distance and 1.5 inch creepage distance.
The minimum clearance of 1.5 inches need not apply to through bolts in
metallic contact with equipment cases or metal parts thereof nor to through
bolts supporting heel arms, provided the portion of such through bolts extending
into the climbing space is covered with non–conducting material as specified in
Rule 22.2 .
Strikeout and Underline Version
Rule 58.1-B3
58.1-B3)
From Hardware: Equipment cases, hangers, and other
metal parts in contact therewith shall clear through bolts, arm braces of metal,
and other hardware elements, by not less than 1.5 inches; except that such cases
and hangers shall clear crossarm braces and crossarm through bolts by not less
than 1 inch air–gap distance and 1.5 inch creepage distance.
The minimum clearance of 1.5 inches need not apply to through bolts in
metallic contact with equipment cases or metal parts thereof nor to through
bolts supporting heel arms, provided the portion of such through bolts extending
into the climbing space is covered with non–conducting material as specified in
Rule 22.2 22.8.
Final Version
Rule 58.1-B3
58.1-B3)
From Hardware: Equipment cases, hangers, and other
metal parts in contact therewith shall clear through bolts, arm braces of metal,
and other hardware elements, by not less than 1.5 inches; except that such cases
and hangers shall clear crossarm braces and crossarm through bolts by not less
than 1 inch air–gap distance and 1.5 inch creepage distance.
The minimum clearance of 1.5 inches need not apply to through bolts in
metallic contact with equipment cases or metal parts thereof nor to through
bolts supporting heel arms, provided the portion of such through bolts extending
into the climbing space is covered with non–conducting material as specified in
Rule 22.8