Rule 86.4-D2

 

86.4-D2)    Passing And Attached To Same Pole: Where a guy of a communication system and a guy of a supply system pass each other and are attached to the same pole, a separation of not less than 3 inches shall be maintained between such guys. No separation is required between such guys of communication systems, provided neither is an exposed guy (see Rule 21.3-C).

  

 

Strikeout and Underline Version

Rule 86.4-D2

 

86.4-D2)    Passing And Attached To Same Pole: Where a guy of a communication system and a guy of a supply system pass each other and are attached to the same pole, a separation of not less than 3 inches shall be maintained between such guys. No separation is required between such guys of communication systems, provided neither is an exposed guy (see Rule 21.3-C 21.5-C).

 

Final Version

Rule 86.4-D2

 

86.4-D2)    Passing And Attached To Same Pole: Where a guy of a communication system and a guy of a supply system pass each other and are attached to the same pole, a separation of not less than 3 inches shall be maintained between such guys. No separation is required between such guys of communication systems, provided neither is an exposed guy (see Rule 21.5-C).