Changes Shown with Strikeout / Underline
84.4 Clearances
E. Above
alongside or in Immediate Proximity to Buildings, Bridges and Other Structures
Conductors
should be arranged so as not to hamper or endanger firefighters and workers in
performing their duties. The basic
clearances of communication conductors from buildings are specified in Table 1,
Cases 6 and 7, Column B. The
horizontal clearance (Table 1, Case 7) shall be maintained until the
vertical clearance (Table 1, Case 6) is attained (see Figure
84–4 5).
The requirements of Table 1,
Case 7, Column B also apply at fire escapes, windows, doors, and
other points at which entrance or exit might be reasonably expected.
Proposed
Final
84.4 Clearances
E. Above
alongside or in Immediate Proximity to Buildings, Bridges and Other Structures
Conductors
should be arranged so as not to hamper or endanger firefighters and workers in performing
their duties. The basic clearances of communication conductors from buildings
are specified in Table 1, Cases 6 and 7, Column B. The horizontal clearance (Table 1, Case 7)
shall be maintained until the vertical clearance (Table 1, Case 6) is attained
(see Figure 84–5). The
requirements of Table 1, Case 7, Column B also apply at fire escapes,
windows, doors, and other points at which entrance or exit might be reasonably
expected.