Original Version
Rule 54.9-E1
54.9-E1) With Guard Arm Below Conductors of 750-20,000
Volts: The vertical clearance between the top conductor in a rack group
and conductors of 750-20,000 volts at the next conductor level above, may
be less than 6 feet but shall be not less than 4 feet. If a clearance
of less than 6 feet is used, all of the following requirements:
A wood guard arm not less than 48 inches long shall be installed
directly above and parallel to the top line conductor of such a rack group;
Conductors in such a rack group, which are so guarded, shall not be attached
to more than one side (there being four sides) of any pole; and
No service drop conductors supported on such rack shall pass between the
surface of pole and the vertical plane of the line conductors. Any
service drop conductors attached to and supported by the line conductors
shall have a clearance of not less than 15 inches from surface of pole.
(See App. G, Fig 43.)
Each guard arm and its pole attachments are required by Rule 46 to withstand
a vertical load of 200 pounds at either end.
Strikeout and Underline Version
Rule 54.9-E1
54.9-E1) With Guard Arm Below Conductors of 750-
20,000 21,000 Volts: The vertical clearance between
the top conductor in a rack group and conductors of 750-20,000
21,000 volts at the next conductor level above, may be less than
6 feet but shall be not less than 4 feet. If a clearance of less than
6 feet is used, all of the following requirements:
A wood guard arm not less than 48 inches long shall be
installed directly above and parallel to the top line conductor of such a
rack group;
Conductors in such a rack group, which are so guarded, shall not be attached
to more than one side (there being four sides) of any pole; and
No service drop conductors supported on such rack shall pass between the
surface of pole and the vertical plane of the line conductors. Any
service drop conductors attached to and supported by the line conductors
shall have a clearance of not less than 15 inches from surface of pole.
(See App. G, Fig 43.)
Each guard arm and its pole attachments are required by Rule 46 to withstand a vertical load of 200 pounds at either end.
Final Version
Rule 54.9-E1
54.9-E1) With Guard Arm Below Conductors of
750-21,000 Volts: The vertical clearance between the top conductor
in a rack group and conductors of 750-21,000 volts at the next conductor
level above, may be less than 6 feet but shall be not less than 4 feet.
If a clearance of less than 6 feet is used, all of the following requirements:
A wood guard arm not less than 48 inches long shall
be installed directly above and parallel to the top line conductor of such
a rack group;
Conductors in such a rack group, which are so guarded, shall not be attached
to more than one side (there being four sides) of any pole; and
No service drop conductors supported on such rack shall pass between the
surface of pole and the vertical plane of the line conductors. Any
service drop conductors attached to and supported by the line conductors
shall have a clearance of not less than 15 inches from surface of pole.
(See App. G, Fig 43.)
Each guard arm and its pole attachments are required by Rule 46 to withstand
a vertical load of 200 pounds at either end.