Original Version
Rule 58.4-B3b
58.4-B3b) From Conductors in Excess of 750 Volts Below:
The vertical clearance of capacitor and regulator cases and their hangers
from the level of conductors in excess of 750 volts below shall be not less
than
12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-20,000 and
24 inches for conductors of 20,000 -35,000 volts.
Strikeout and Underline Version
Rule 58.4-B3b
58.4-B3b) From Conductors in Excess of 750 Volts
Below: The vertical clearance of capacitor and regulator cases and their
hangers from the level of conductors in excess of 750 volts below shall be
not less than
12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-20,000 21,000 and
24 inches for conductors of 20,00021,000-35,000
volts.
Final Version
Rule 58.4-B3b
58.4-B3b) From Conductors in Excess of 750
Volts Below: The vertical clearance of capacitor and regulator cases and
their hangers from the level of conductors in excess of 750 volts below shall
be not less than
12 inches for conductors of 750-7500 volts,
18 inches for conductors of 7500-21,000 and
24 inches for conductors of21,000-35,000 volts.