Original Version
Rule 56.6-B
56.6-B. Guys To Arms Supporting Conductors of Less Than 22,500 Volts
All portions of arm guys within 6 feet of points of attachment to wood crossarms, or metal crossarms on wood poles, shall not be grounded if the crossarms support supply conductors of less than 22,500 volts. Where necessary to avoid the grounding of such portions, arm guys shall be sectionalized by means of insulators at locations as specified in Rule 56.7.
Strikeout and Underline Version
Rule 56.6-B
56.6-B.
Guys To Arms Supporting Conductors of
Less Than 22,500 35,500 Volts
All portions of arm guys within 6
feet of points of attachment to wood crossarms, or metal crossarms on wood
poles, shall not be grounded if the crossarms support supply conductors of less
than 22,500 35,500 volts.
Where necessary to avoid the grounding of such portions, arm guys shall
be sectionalized by means of insulators at locations as specified in Rule 56.7.
Final Version
Rule 56.6-B
56.6-B. Guys To Arms Supporting Conductors of Less Than 35,500 Volts
All portions of arm guys within 6 feet of points of attachment to wood crossarms, or metal crossarms on wood poles, shall not be grounded if the crossarms support supply conductors of less than 35,500 volts. Where necessary to avoid the grounding of such portions, arm guys shall be sectionalized by means of insulators at locations as specified in Rule 56.7.