Rule 56.6-B

 

56.6-B.    Guys To Arms Supporting Conductors of Less Than 22,500 Volts

 

All portions of arm guys within 6 feet of points of attachment to wood crossarms, or metal crossarms on wood poles, shall not be grounded if the crossarms support supply conductors of less than 22,500 volts.  Where necessary to avoid the grounding of such portions, arm guys shall be sectionalized by means of insulators at locations as specified in Rule 56.7.

 

Strikeout and Underline Version

Rule 56.6-B

 

 

56.6-B.    Guys To Arms Supporting Conductors of Less Than 22,500 35,500  Volts

 

All portions of arm guys within 6 feet of points of attachment to wood crossarms, or metal crossarms on wood poles, shall not be grounded if the crossarms support supply conductors of less than 22,500 35,500 volts.  Where necessary to avoid the grounding of such portions, arm guys shall be sectionalized by means of insulators at locations as specified in Rule 56.7.

 

Final Version

Rule 56.6-B

 

 

56.6-B.    Guys To Arms Supporting Conductors of Less Than 35,500 Volts

 

All portions of arm guys within 6 feet of points of attachment to wood crossarms, or metal crossarms on wood poles, shall not be grounded if the crossarms support supply conductors of less than 35,500 volts.  Where necessary to avoid the grounding of such portions, arm guys shall be sectionalized by means of insulators at locations as specified in Rule 56.7.