Change List for this Rule

 

Original Version

Rule 84.6-B

 

84.6-B.    Ground Wires

 

Ground wires, other than lightning protection wires not attached to equipment or ground wires on grounded structures, shall be covered by metal pipe or suitable covering of wood or metal or of plastic pipe material designated as Type II in the standard specified in Rule 22.2, for a distance above ground sufficient to protect against mechanical injury, but in no case shall such distance be less than 7 feet. Such covering may be omitted providing the ground wire in this 7-foot section has a mechanical strength at least equal to the strength of No.6 AWG medium-hard-drawn copper.

 

Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).

 

Strikeout and Underline Version

Rule 84.6-B

 

84.6-B.    Ground Wires

 

Ground wires, other than lightning protection wires not attached to equipment or ground wires on grounded structures, shall be covered by metal pipe or suitable covering of wood or metal or of plastic pipe material designated as Type II in the standard specified in Rule 22.2-C, for a distance above ground sufficient to protect against mechanical injury, but in no case shall such distance be less than 7 feet. Such covering may be omitted providing the ground wire in this 7-foot section has a mechanical strength at least equal to the strength of No.6 AWG medium-hard-drawn copper.

 

Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).

 

Final Version

Rule 84.6-B

 

84.6-B.    Ground Wires

 

Ground wires, other than lightning protection wires not attached to equipment or ground wires on grounded structures, shall be covered by metal pipe or suitable covering of wood or metal or of plastic pipe material specified in Rule 22.2-C, for a distance above ground sufficient to protect against mechanical injury, but in no case shall such distance be less than 7 feet. Such covering may be omitted providing the ground wire in this 7-foot section has a mechanical strength at least equal to the strength of No.6 AWG medium-hard-drawn copper.

 

Portions of ground wires which are on the surface of wood poles and within 6 feet vertically of unprotected supply conductors supported on the same pole, shall be covered with a suitable protective covering (see Rule 22.2).