84.8-C3) Above Ground In Areas Accessible To Pedestrians Only:
a) Industrial and Commercial Premises: Over areas accessible to pedestrians only, service drops shall have a vertical clearance of not less than 12 feet.
b) Residential Premises: Over areas accessible to pedestrians only, service drops shall be maintained at a vertical clearance of not less than 10 feet. If the building served does not permit an attachment which will provide this 10-foot clearance without the installation of a structure on the building, the clearance shall be as great as possible but in no case less than 8 feet 6 inches.
c) Above Ground on Fenced Railway Rights-of-Way: Service drops to railway signal devices shall be maintained at clearances as specified in Rule 84.4-A4. Service drops which are entirely on affected railway rights-of-way in areas accessible to pedestrians only may have clearances above ground less than as specified in Table 1, Column B, Case 5 (10 feet), but not less than 7 feet.
Strikeout and Underline Version
Rule 84.8-C3
84.8-C3) Above Ground In Areas Accessible To Pedestrians Only:
a)
Industrial and Commercial Premises: Over
areas accessible to pedestrians only, service drops the vertical
clearance shall have a vertical clearance of not be less than
12 feet.
b)
Residential Premises: Over areas
accessible to pedestrians only, service drops the shall not
be maintained at a vertical clearance of not less than 10 feet.
EXCEPTION: If the building served does not permit an attachment which will provide this 10-foot clearance without the installation of a structure on the building, the clearance shall be as great as possible but in no case less than 8 feet 6 inches.
c)
Above Ground on Fenced Railway
Rights-of-Way: (See Rule 84.4-A4) Service drops to railway signal
devices shall be maintained at clearances as specified in Rule 84.4-A4. Service
drops which are entirely on affected railway rights-of-way in areas accessible
to pedestrians only may have clearances above ground less than as specified in
Table 1, Column B, Case 5 (10 feet), but not less than 7 feet.
Final Version
Rule 84.8-C3
84.8-C3) Above Ground In Areas Accessible To Pedestrians Only:
a) Industrial and Commercial Premises: Over areas accessible to pedestrians only, the vertical clearance shall not be less than 12 feet.
b) Residential Premises: Over areas accessible to pedestrians only, the shall not be less than 10 feet.
EXCEPTION: If the building served does not permit an attachment which will provide this 10-foot clearance without the installation of a structure on the building, the clearance shall be as great as possible but in no case less than 8 feet 6 inches.
c) Above Ground on Fenced Railway Rights-of-Way: (See Rule 84.4-A4)