General Order 64-A
Section V
Detailed Construction Requirements For Supply Lines
(Class H, L and T Circuits)
52.7 Buck Arms.
A.
One Voltage Classification.
In Systems where circuits of one
voltage classification only are carried on same line crossarms, related buck
arms (see Rule 20.8-B) may be attached to the pole at a distance to afford the
conductor clearance of Table 2, Case 14.
The clearance of Case 8 to 13, inclusive, shall apply between the
conductors on such line or buck arms and the conductors on the line or buck
arms at the next conductor level above or below.
B.
Combination.
In systems where circuits of
0-750 volts and 750-7500 volts are carried on same line crossarms, related buck
arms may be attached to the pole at a minimum 2 foot vertical separation,
provided the conductors of these 2 voltages classifications are installed on
opposite ends of the crossarm with a minimum horizontal separation of 42
inches. This 2 foot clearance shall
apply between the conductors on such line or buck arms and the conductors on
the line or buck arms at the next conductor level above or below.