General Order 64-A
Section V
Detailed Construction Requirements For Supply Lines
(Class H, L and T Circuits)
57.7 Protection.
A.
Cables (See
Rule 54.6-B.)
Cables which are grounded may be
attached directly to surface of poles and installed at a distance less than 6
feet below different circuits of open wire supply conductors. Where so installed, they shall be protected
by a guard arm at least 4 feet in length, placed as close to them and as nearly
parallel with them as practicable. In
lieu of the guard arm, a suitable insulating covering of the length specified
may be placed around the cable and supporting messenger. (See Rule 58.1 for cable terminals; also
App. G, Fig 87.)
B. Messengers.
Messengers which are grounded,
where dead-ended or wrapped around a pole, shall be at least 6 feet vertically
below supply conductors of other circuits.
Should it be impracticable to maintain such vertical clearance, a
reduction to 4 feet below supply conductors of 0-750 volts will be permitted,
provided the messenger is suitably guarded with the equivalent of double guard
arms placed directly above it and substantially parallel with it.