General Order 64-A
Section VII
Detailed Construction Requirements For Trolley Lines
(Class T Circuits)
76.7 From Level of 17,000 Volts or More.
Guys from the level of conductors
of 17,000 volts or more shall have their lower ends permanently grounded,
either through the medium of metal poles, ground wires or anchor guys, provided
the clearances of guys and conductors specified in Rule 56.6-D1 and Rule
56.6-D2 can be maintained.