General Order 64-A
Section VIII
Detailed Construction Requirements For Communication Lines
(Class C Circuits)
86.5 Fastenings.
Guy wires where attached to
anchor rods shall be protected by the use of guy thimbles or their
equivalent. Cedar and other soft-wood
poles to which any guy having an ultimate strength of 5000 pounds or more is
attached, shall be protected by suitable guy shim, and where necessary, with
hooks lag bolts or other equivalent means to prevent the guy from slipping
along the pole.