General Order 64-A
Section IX
Joint Poles Or Poles Jointly Used
93
Messengers.
Messengers which are grounded
shall, where dead-ended or wrapped around a pole for any reason, be at least 6
feet vertically below all supply conductors of other circuits. Should it be impracticable to maintain such
vertical clearance, a reduction to 4 feet below supply conductors of 0-750
volts will be permitted, provided the messenger is suitably guarded with the equivalent
of double guard arms placed directly above it and substantially parallel to it.