General Order 64-A
Section X
Supply And Communication Lines In Crossings Or Conflicts
103.4 Short Spans.
In cases where the crossing span
is constructed of such height that its length is less than the distance between
either point of support of its lowest conductor and the highest conductor of
the line crossed, the requirements for conductor sag and for size and type of
the conductors required are waived, provided that a permanently grounded guard
arm is installed at each crossing support in such a manner as to prevent the
conductors which may break from swinging back into the conductors of span
crossed over.