General Order 64-A
Appendix
B
Mechanical And Loading Data For Conductors
TABLE 19 CHARACTERISTICS OF HARD DRAWN COPPER COVERED STEEL WIRE – SOLID – BAR WIND AND ICE LOADS |
|||||||||
Size A.W.G |
Diameter, inches |
Area of conductor Square Inch |
Ultimate tension in pounds |
Loading Per Linear Foot of Conductor, Pounds |
|||||
Light Loading District |
Heavy Loading District |
||||||||
Vertical – Conductor only |
Horizontal -Wind, 8 lbs per square foot |
Resultant Load |
Vertical, Conductor +½ inch Ice |
Horizontal -Wind 6 Lbs per Sq. Ft. on Conductor + ½ inch Ice |
Resultant Load |
||||
0 |
0.325 |
0.0829 |
5,700 |
0.293 |
0.216 |
0.364 |
0.805 |
0.662 |
1.040 |
1 |
.289 |
.0657 |
4,800 |
.231 |
.192 |
.300 |
.720 |
.644 |
0.965 |
2 |
.258 |
.0521 |
4,000 |
.184 |
.172 |
.252 |
.654 |
.629 |
.907 |
4 |
.204 |
.0328 |
2,650 |
.116 |
.136 |
.179 |
.552 |
.602 |
.817 |
6 |
.162 |
.0206 |
1,800 |
.073 |
.108 |
.130 |
.484 |
.581 |
.756 |
8 |
.128 |
.0129 |
1,200 |
.046 |
.085 |
.096 |
.435 |
.564 |
.713 |
9 |
.114 |
.0102 |
970 |
.037 |
.076 |
.085 |
.418 |
.557 |
.696 |
10 |
.102 |
.0081 |
800 |
.029 |
.068 |
.074 |
.402 |
.551 |
.682 |
12 |
.081 |
.0052 |
520 |
.018 |
.054 |
.057 |
.379 |
.540 |
.660 |