Previous Code

Main Page

GO 95 Startup Page

Change List for this Rule

Search GO 95

Section Main Page

Next Code

 

General Order 95

 

Section III

 

Requirements for All Lines

 

38    Minimum Clearances of Wires from Other Wires

 

The minimum vertical, horizontal or radial clearances of wires from other wires shall not be less than the values given in Table 2 and are based on a temperature of 60° F. and no wind. Conductors may be deadended at the crossarm or have reduced clearances at points of transposition, and shall not be held in violation of Table 2, Cases 8–15 , inclusive.

 

The clearances in Table 2 shall in no case be reduced more than 10 percent, except mid-span in Tier 3 of the High Fire-Threat District where they shall be reduced by no more than 5 percent, because of temperature and loading as specified in Rule 43 or because of a difference in size or design of the supporting pins, hardware or insulators. All clearances of less than 5 inches shall be applied between surfaces, and clearances of 5 inches or more shall be applied to the center lines of such items. The utilities of interest (including electric supply and/or communication companies) shall cooperate and provide relevant information for sag calculations for their facilities, upon request.

 

Note:    Revised May 22, 1990 by Resolution No. SU–5, December 21, 2017 by Decision 17-12-024.