Change List for this Rule

 

General Order 95

 

Section IX

 

Joint Poles or Poles Jointly Used

 

93    Climbing Space

 

Climbing space shall be provided on all jointly used poles which support conductors and the provisions of Rules 54.7 and 84.7 are directly applicable to such poles. Climbing space on jointly used poles shall be so correlated between conductor levels that its position in relation to the pole is not changed by more than 90 degrees in a vertical distance of less than 8 feet. Climbing space shall be maintained from the ground level.

 

Note:    Revised May 22, 1990 by Resolution No. SU–5.