93 Climbing Space
Climbing space shall be provided on all jointly used poles which
support conductors and the provisions of Rules
54.7
and 84.7
are directly applicable to such poles. Climbing space on jointly used poles
shall be so correlated between conductor levels that its position in relation
to the pole is not changed by more than 90 degrees in a vertical distance
of less than 8 feet. Climbing space shall be maintained from the ground level.