General Order 95
Appendix B
Mechanical and Loading Data for Conductor
Table 20 Copper Wire - Stranded and Solid - Triple Braid
Weatherproof - Characteristics and Loading |
||||||||||||
Characteristics of Conductor |
Loading Per Linear Foot of Conductor, Pounds |
|||||||||||
Size of Cable or Wire, Clr. Mils or AWG |
Component Wires(Strands) |
Diameter With Covering Inches * |
AreaWithout CoveringSquare Inch |
Ultimate Tensile Strength, Pounds |
Light Loading District |
Heavy Loading District |
||||||
Number |
Diameter,Inch |
HardDrawn ** |
Medium HardDrawn *** |
Vertical Load, Conductor Only |
Horizontal Load, Wind of8 Lbs per Sq. Ft. on Conductor |
Resultant Load |
Vertical Load, Conductor with ½” of Ice
|
Horizontal Load, Wind of6 Lbs per Sq. Ft. on Conductor
with ½” of Ice |
Resultant Load |
|||
1,000,000 |
61 |
0.1280 |
1.656 |
0.7854 |
45,030 |
37,210 |
3.764 |
1.1041 |
3.836 |
5.0146 |
1.3280 |
5.188 |
750,000 |
61 |
.1109 |
1.380 |
.5890 |
34,090 |
28,272 |
2.822 |
.9200 |
2.968 |
3.9910 |
1.1900 |
4.165 |
500,000 |
37 |
.1162 |
1.250 |
.3927 |
22,510 |
18,726 |
1.894 |
.8334 |
2.069 |
2.9822 |
1.1250 |
3.187 |
350,000 |
19 |
.1357 |
1.000 |
.2749 |
15,590 |
13,024 |
1.345 |
.6667 |
1.501 |
2.2777 |
1.0000 |
2.488 |
250,000 |
19 |
.1147 |
.850 |
.1964 |
11,365 |
9,366 |
0.9850 |
.5667 |
1.136 |
1.8244 |
0.9250 |
2.045 |
0000 |
7 |
.1739 |
.805 |
.1662 |
9,154 |
7,772 |
.8000 |
.5367 |
0.963 |
1.6114 |
.9025 |
1.847 |
000 |
7 |
.1548 |
.710 |
.1318 |
7,366 |
6,204 |
.6530 |
.4734 |
.807 |
1.4054 |
.8550 |
1.645 |
00 |
7 |
.1379 |
.660 |
.1045 |
5,925 |
4,952 |
.5220 |
.4400 |
.683 |
1.2433 |
.8300 |
1.495 |
0 |
7 |
.1228 |
.610 |
.0829 |
4,753 |
3,953 |
.4240 |
.4067 |
.588 |
1.1142 |
.8050 |
1.375 |
1 |
7 |
.1093 |
.509 |
.0657 |
3,802 |
3,154 |
.3280 |
.3394 |
.472 |
0.9554 |
.7545 |
1.217 |
2 |
7 |
.0974 |
.488 |
.0521 |
3,042 |
2,517 |
.2700 |
.3253 |
.423 |
.8843 |
.7440 |
1.156 |
4 |
7 |
.0772 |
.390 |
.0328 |
1,940 |
1,604 |
.1700 |
.2600 |
.311 |
.7234 |
.6950 |
1.003 |
4 |
1 |
- |
.387 |
.03278 |
1,970 |
1,642 |
.1665 |
.2580 |
.307 |
.7180 |
.6935 |
0.998 |
6 |
1 |
- |
.347 |
.0206 |
1,280 |
1,046 |
.1136 |
.2313 |
.258 |
.6403 |
.6735 |
.929 |
8 |
1 |
- |
.294 |
.1297 |
826 |
667 |
.0760 |
.1960 |
.210 |
.5697 |
.6470 |
.862 |
* Average outside diameter observed commercially.
** Minimum ultimate strengths of ASTM Specifications, B
1 - 39.
*** For stranded conductors, 90% minimum ultimate strength
of ASTM Specifications, B 2 - 39, plus ¼ of the difference between
maximum and 90% of minimum ASTM values; for solid conductors, minimum ultimate
strengths of ASTM Specifications, B 2 39, plus ¼ of the difference
between minimum and maximum.