Section
III
Requirements for All Lines
32.3 Colinear Lines
The center-line clearance between poles and conductors which pass unattached shall not be less than 1 ½ times the clearance specified in Table 1, Case 8, except where the interest pole is within 10 feet apart, clearances not less than as specified in Table 1, Case 8 shall be maintained between the center line of any pole and conductors which pass unattached. Where clearance crossarms are installed in the construction and maintenance of collinear lines or crossings, clearances not less than as specified in Table 1, Case 8 shall be maintained between all conductors on the clearance crossarms and the center line of poles to which such crossarms are attached.
The provisions of the foregoing rules for collinear lines are subject to modifications specified in Rule 84.4-D3 where communication circuits only are concerned.