Rule 92.1-A
92.1-A.    Between Low Voltage Rack Conductors
and Other Conductors
On jointly used poles, the following minimum vertical clearances shall apply between 0-750 volt supply conductors in rack construction and other conductors (see App. G, Fig 9):
| Racks above | |
| Conductors or cables 15’’ or more from center line of pole | 4 feet | 
| Unguarded cables, messengers or racks attached to poles | 6 feet | 
| Guarded cables, messengers, or racks attached to poles | 4 feet | 
| Unguarded racks below | |
| All circuits | 6 feet | 
| Guarded rack below | |
| Circuits of 0-21,000 volts or communication circuits | 4 feet | 
      
Strikeout and Underline Version
Rule 92.1-A
      
92.1-A.    Between Low Voltage Rack Conductors
and Other Conductors
      
On jointly used poles, the following minimum vertical clearances
shall apply between 0-750 volt supply conductors in rack construction and
other conductors (see App. G, Fig 9):
                  
    
| Racks above | |
| Conductors or cables 15’’ or more from center line of pole | 4 feet | 
| Unguarded cables, messengers or racks attached to poles | 6 feet | 
| Guarded cables, messengers, or racks attached to poles | 4 feet | 
| Unguarded racks below | |
| All circuits | 6 feet | 
| Guarded rack below | |
| Circuits of 0- | 4 feet | 
Final Version
Rule 92.1-A
            
92.1-A.    Between Low Voltage Rack Conductors
and Other Conductors
            
On jointly used poles, the following minimum vertical clearances shall apply between 0-750 volt supply conductors in rack construction and other conductors (see App. G, Fig 9 ):
| Racks above | |
| Conductors or cables 15’’ or more from center line of pole | 4 feet | 
| Unguarded cables, messengers or racks attached to poles | 6 feet | 
| Guarded cables, messengers, or racks attached to poles | 4 feet | 
| Unguarded racks below | |
| All circuits | 6 feet | 
| Guarded rack below | |
| Circuits of 0-22,500 volts or communication circuits | 4 feet |