Original Version
Rule 92.1-F2
92.1-F2)    Cable Terminals or Metal Boxes: On jointly used poles 
metal communication cable terminals, metal boxes or similar equipment which are 
less than 8 inches from center line of pole or are attached to surface of pole 
shall be placed not less than 6 feet vertically below or 3 feet above the level 
of the nearest unprotected supply conductor. 
All parts of such metal terminals, boxes or similar equipment which 
are 8 inches or more from center line of pole shall have vertical clearances 
from conductors not less than the clearance specified in Table 2, Col. C, Cases 8 to 13 
inclusive.
For clearance between street light drop wires and cables, 
other conductors, and metal boxes see Rules 58.2-B3 and 92.1-F5.
Strikeout and Underline Version
Rule 92.1-F2
92.1-F2)    Cable Terminals or Metal Boxes: On jointly used poles 
metal communication cable terminals, metal boxes or similar equipment which are 
less than 8 inches from center line of pole or are attached to surface of pole 
shall be placed not less than 6 feet vertically below or 3 feet above the level 
of the nearest unprotected supply conductor. 
All parts of such metal terminals, boxes or similar equipment which 
are 8 inches or more from center line of pole shall have vertical clearances 
from conductors not less than the clearance specified in Table 2, Col. C, Cases 8 to 13 
inclusive.
For clearance between street light drop wires and cables, 
other conductors, and metal boxes see Rules 58.2-B3 
58.5-B3 and 92.1-F5.
Final Version
Rule 92.1-F2
92.1-F2)    Cable Terminals or Metal Boxes: On jointly used poles 
metal communication cable terminals, metal boxes or similar equipment which are 
less than 8 inches from center line of pole or are attached to surface of pole 
shall be placed not less than 6 feet vertically below or 3 feet above the level 
of the nearest unprotected supply conductor. 
All parts of such metal terminals, boxes or similar equipment which 
are 8 inches or more from center line of pole shall have vertical clearances 
from conductors not less than the clearance specified in Table 2, Col. C, Cases 8 to 13 
inclusive.
For clearance between street light drop wires and cables, 
other conductors, and metal boxes see Rules 58.5-B3 and 92.1-F5.