Original Version
Rule 54.8-B3
54.8-B3)
Above Ground in Areas Accessible to
Pedestrians Only:
Over
areas accessible to pedestrians only service drops shall be maintained at a
vertical clearance of not less than 12 feet.
EXCEPTION: This clearance may be reduced for insulated services that conform with rule 20.8-G, to not less than 8 feet 6 inches.
Strikeout and Underline Version
Rule 54.8-B3
54.8-B3)
Above Ground in Areas Accessible to
Pedestrians Only:
Over
areas accessible to pedestrians only service drops shall be maintained at a
vertical clearance of not less than 12 feet.
EXCEPTION:
This
clearance may be reduced for insulated services that conform with rule 20.8-G
54.8-A, to not less than 8 feet 6 inches.
Final Version
Rule 54.8-B3
54.8-B3)
Above Ground in Areas Accessible to
Pedestrians Only:
Over
areas accessible to pedestrians only service drops shall be maintained at a
vertical clearance of not less than 12 feet.
EXCEPTION: This clearance may be reduced for insulated services that conform with Rule 54.8–A, to not less than 8 feet 6 inches.