Rule 54.8-B3

 

54.8-B3)    Above Ground in Areas Accessible to Pedestrians Only:

Over areas accessible to pedestrians only service drops shall be maintained at a vertical clearance of not less than 12 feet.

 

EXCEPTION:    This clearance may be reduced for insulated services that conform with rule 20.8-G, to not less than 8 feet 6 inches.

 

Strikeout and Underline Version

Rule 54.8-B3

 

54.8-B3)    Above Ground in Areas Accessible to Pedestrians Only:

Over areas accessible to pedestrians only service drops shall be maintained at a vertical clearance of not less than 12 feet.

 

EXCEPTION:    This clearance may be reduced for insulated services that conform with rule 20.8-G 54.8-A, to not less than 8 feet 6 inches.

 

Final Version

Rule 54.8-B3

 

54.8-B3)    Above Ground in Areas Accessible to Pedestrians Only:

Over areas accessible to pedestrians only service drops shall be maintained at a vertical clearance of not less than 12 feet.

 

EXCEPTION:    This clearance may be reduced for insulated services that conform with Rule 54.8–A, to not less than 8 feet 6 inches.