84.7-E.    Allowable Climbing Space Obstructions

 

Vertical conductors, when in a suitable protective covering attached directly to the surface of the pole, terminal boxes or similar equipment which do not extend more than 5 inches from the surface of the pole, and guys, will not be held to obstruct the climbing space provided not more than two guys (provided they are separated at the pole by a vertical distance of not more than 18 inches) and one other of the above named obstructions are installed in any 4-foot vertical section of climbing space.

 

Crossarms and their supporting members are allowed in climbing spaces provided that, where buck arms are involved, any arms within climbing spaces are treated as double arms.

 

A guard arm, a longitudinal run of messenger, cable or insulated wire will not be held to obstruct the climbing space where they are placed in the climbing space because the presence of a building wall or similar obstacle will not permit the cable to be placed on the side of pole opposite the climbing space.  Pole steps shall be suitably placed for the purpose of facilitating climbing past the level of terminal box, cable, drop wires and guard arm.

 

Unnecessary impairment of the climbing space is not permitted by the application of this Rule 84.7-E.

 

Strikeout and Underline Version

Rule 84.7-E

 

84.7-E.    Allowable Climbing Space Obstructions

 

Vertical conductors, when in a suitable protective covering attached directly to the surface of the pole, terminal boxes or similar equipment which do not extend more than 5 inches from the surface of the pole, and guys, will not be held to obstruct the climbing space provided not more than two guys (provided they are separated at the pole by a vertical distance of not more than 18 inches) and one other of the above named obstructions are installed in any 4-foot vertical section of climbing space.

 

Crossarms and their supporting members are allowed in climbing spaces provided that, where buck arms are involved, any arms within climbing spaces are treated as double arms.

 

A guard arm, a longitudinal run of messenger, cable or insulated wire will not be held to obstruct the climbing space where they are placed in the climbing space because the presence of a building wall or similar obstacle will not permit the cable to be placed on the side of pole opposite the climbing space.  Pole steps shall be suitably placed for the purpose of facilitating climbing past the level of terminal box, cable, drop wires and guard arm.

 

Pole restoration techniques are allowed in climbing space provided pole steps are placed in the restoration area as part of the process.  Pole stepping shall be in accordance with Rules 51.7 and 81.6.  Hardware for the use of detachable pole steps shall be installed as part of the restoration process from ground line to 7 feet 6 inches.

 

Bands limited to 6 inches in total width are allowed in any 24-inch section of climbing space.  These limitations are excluded for pole stubbing and pole splicing bands when pole step provisions are installed.

 

Unnecessary impairment of the climbing space is not permitted by the application of this Rule 84.7-E.

 

Final Version

Rule 84.7-E

 

84.7-E.    Allowable Climbing Space Obstructions

 

Vertical conductors, when in a suitable protective covering attached directly to the surface of the pole, terminal boxes or similar equipment which do not extend more than 5 inches from the surface of the pole, and guys, will not be held to obstruct the climbing space provided not more than two guys (provided they are separated at the pole by a vertical distance of not more than 18 inches) and one other of the above named obstructions are installed in any 4-foot vertical section of climbing space.

 

Crossarms and their supporting members are allowed in climbing spaces provided that, where buck arms are involved, any arms within climbing spaces are treated as double arms.

 

A guard arm, a longitudinal run of messenger, cable or insulated wire will not be held to obstruct the climbing space where they are placed in the climbing space because the presence of a building wall or similar obstacle will not permit the cable to be placed on the side of pole opposite the climbing space.  Pole steps shall be suitably placed for the purpose of facilitating climbing past the level of terminal box, cable, drop wires and guard arm.

 

Pole restoration techniques are allowed in climbing space provided pole steps are placed in the restoration area as part of the process.  Pole stepping shall be in accordance with Rules 51.7 and 81.6.  Hardware for the use of detachable pole steps shall be installed as part of the restoration process from ground line to 7 feet 6 inches.

 

Bands limited to 6 inches in total width are allowed in any 24-inch section of climbing space.  These limitations are excluded for pole stubbing and pole splicing bands when pole step provisions are installed.

 

Unnecessary impairment of the climbing space is not permitted by the application of this Rule 84.7-E.