Original Version
Rule 32.4-C
32.4-C. Supply Circuits and Private Communication Circuits (see Rules 20.5-A and 89)
(1) 7500-22,500 Volts, Same Ownership: Supply circuits of 7500-22,500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A1.
(2) 750-7500 Volts, Same Ownership: Supply circuits of 750-7500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A2.
(3) 0-750 Volts: Supply circuits of 0-750 volts and private communication circuits may be supported on the same crossarms as provided in Rule 89.2-A3, or Rule 89.2-A4.
Strikeout and Underline Version
Rule 32.4-C
32.4-C. Supply Circuits and
Private Communication Circuits (see Rules20.6-A 20.5-A and 89)
(1) 7500-22,500 Volts, Same Ownership: Supply circuits of 7500-22,500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A1.
(2) 750-7500 Volts, Same Ownership: Supply circuits of 750-7500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A2.
(3) 0-750 Volts: Supply circuits of 0-750 volts and private communication circuits may be supported on the same crossarms as provided in Rule 89.2-A3, or Rule 89.2-A4.
Final Version
Rule 32.4-C
32.4-C. Supply Circuits and Private Communication Circuits (see Rules 20.6-A and 89)
(1) 7500-22,500 Volts, Same Ownership: Supply circuits of 7500-22,500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A1.
(2) 750-7500 Volts, Same Ownership: Supply circuits of 750-7500 volts and private communication circuits owned (or leased) and operated and maintained by the same organization may be supported on the same crossarms as provided in Rule 89.2-A2.
(3) 0-750 Volts: Supply circuits of 0-750 volts and private communication circuits may be supported on the same crossarms as provided in Rule 89.2-A3, or Rule 89.2-A4.