Rule 43.2-C

43.2-C Temperature
Temperature shall be considered to be 25F at the time of maximum loading. The normal temperature for computing erection conditions is 60 F. Maximum temperature shall be assumed as 130Fin computing sag under this condition.

Strikeout and Underline Version
Rule 43.2-C

43.2-C Temperature
Conductor temperature shall be considered assumed to be 25 F at the time of maximum loading. The normal A conductor temperature of at least 130F shall also be assumed for computing erection conditions is 60 F. Maximum temperature shall be assumed as 130F in computing sag under this conditionand its effect on structural loads due to weight span.

Final Version
Rule 43.2-C

43.2-C Temperature
Conductor temperature shall be assumed to be 25F at the time of maximum loading. A conductor temperature of at least 130F shall also be assumed for computing sag and its effect on structural loads due to weight span.