Previous Rule Change | Main Page | Resolution Decision Main Page | Change List for this Rule | Search Decision Number 14-02-015 | Decision Number 14-02-015 | Next Rule Change |
Original Version
Rule 43.2-C
43.2-C | Temperature |
Temperature shall be considered to be 25°F at the time of maximum loading. The normal temperature for computing erection conditions is 60° F. Maximum temperature shall be assumed as 130°Fin computing sag under this condition. |
Strikeout and Underline Version
Rule 43.2-C
43.2-C | Temperature |
Conductor temperature shall be considered assumed to be 25° F at the time of maximum loading. The normal A conductor temperature of at least 130°F shall also be assumed for computing erection conditions is 60° F. Maximum temperature shall be assumed as 130°F in computing sag under this conditionand its effect on structural loads due to weight span. |
Final Version
Rule 43.2-C
43.2-C | Temperature |
Conductor temperature shall be assumed to be 25°F at the time of maximum loading. A conductor temperature of at least 130°F shall also be assumed for computing sag and its effect on structural loads due to weight span. |