Table 25: Stringing Sags, In Inches, for Communication Conductors In Grade F Construction

Span Length, Feet Light Loading Heavy Loading *
Temperature, Degrees Fahrenheit Temperature, Degrees Fahrenheit
100 80 60 40 20 100 80 60 40 20 0
100 7 6 4.5 4 3.5 9.5 7.5 6 5 4 3.5
120 10.5 8.5 7 5.5 5 13.5 10.5 8.5 7 5.5 4.5
140 14 11 9 7.5 6.5 18.5 14.5 11.5 9.5 7.5 6.5
160 18 15 12 10 8.5 21 18 15 12.5 10.5 9
180 22 18.5 15.5 13 11 26.5 23 19 15.5 13 11
200 27 23 19 16.5 13.5 - - - - - -
220 32.5 27.5 23 20 16.5 - - - - - -
240 36 31.5 27 23.5 20.5 - - - - - -
260 42 37 32 27.5 24 - - - - - -
280 49 42.5 37 32 27.5 - - - - - -
300 56 49 42.5 36.5 32 - - - - - -
* In heavy loading districts, sags of the given values are inadequate for the following conductors and must be increased to meet the safety factor requirements:
Hard–drawn copper, No. 12 AWG in spans greater than 130 feet. Galvanized iron BB, No. 10 BWG in spans greater than 170 feet.
Galvanized iron, EBB, No. 9 BWG in spans greater than 170 feet. Galvanized iron, BB, No. 12 BWG in spans greater than 115 feet.
Galvanized iron, EBB, No 10 BWG in spans greater than 140 feet. Galvanized iron, BB, No. 14 BWG in spans of any length.
Galvanized iron, EBB, No. 12 and No 14 BWG in spans of any length.

Strikeout and Underline Version
Appendix C - Table 25

Table 25 deleted February 5, 2014 by Decision Number 14-02-015: Stringing Sags, In Inches, for Communication Conductors In Grade F Construction

Span Length, Feet Light Loading Heavy Loading *
Temperature, Degrees Fahrenheit Temperature, Degrees Fahrenheit
100 80 60 40 20 100 80 60 40 20 0
100 7 6 4.5 4 3.5 9.5 7.5 6 5 4 3.5
120 10.5 8.5 7 5.5 5 13.5 10.5 8.5 7 5.5 4.5
140 14 11 9 7.5 6.5 18.5 14.5 11.5 9.5 7.5 6.5
160 18 15 12 10 8.5 21 18 15 12.5 10.5 9
180 22 18.5 15.5 13 11 26.5 23 19 15.5 13 11
200 27 23 19 16.5 13.5 - - - - - -
220 32.5 27.5 23 20 16.5 - - - - - -
240 36 31.5 27 23.5 20.5 - - - - - -
260 42 37 32 27.5 24 - - - - - -
280 49 42.5 37 32 27.5 - - - - - -
300 56 49 42.5 36.5 32 - - - - - -
* In heavy loading districts, sags of the given values are inadequate for the following conductors and must be increased to meet the safety factor requirements:
Hard–drawn copper, No. 12 AWG in spans greater than 130 feet. Galvanized iron BB, No. 10 BWG in spans greater than 170 feet.
Galvanized iron, EBB, No. 9 BWG in spans greater than 170 feet. Galvanized iron, BB, No. 12 BWG in spans greater than 115 feet.
Galvanized iron, EBB, No 10 BWG in spans greater than 140 feet. Galvanized iron, BB, No. 14 BWG in spans of any length.
Galvanized iron, EBB, No. 12 and No 14 BWG in spans of any length.