Rule 58.1-A1
58.1
Enclosed Equipment (Transformers,
Capacitors, Regulators, etc.) (For purposes of this rule, enclosed means
encased such as with cases or tanks of equipment operated at greater than 750
volts.)
A. Position
on Pole
(1)
Multiple Units: Where
more than one unit is installed on a pole, they shall be placed on the same
side of the pole. Transformers installed on metal mounting brackets shall not
extend beyond the vertical plane through the centerline of the pole.
Strikeout and Underline Version
Rule 58.1-A1
58.1 Enclosed Equipment (Transformers, Capacitors, Regulators,
etc.) (For purposes of this rule, enclosed means encased such as with cases or
tanks of equipment operated at greater than 750 volts.)
A. Position
on Pole
(1)
Multiple Units: Where
more than one unit is installed on a pole, they shall be placed on the same
side of the pole. Transformers installed on metal mounting brackets shall not
extend beyond the vertical plane through the centerline of the pole.
Exception: Units installed on non-climbable poles may extend beyond
the vertical plane through the centerline of the pole. (See Rule 22.6-D)
Final Version
Rule 58.1-A1
58.1 Enclosed Equipment (Transformers, Capacitors, Regulators,
etc.) (For purposes of this rule, enclosed means encased such as with cases or
tanks of equipment operated at greater than 750 volts.)
A. Position
on Pole
(1)
Multiple Units: Where
more than one unit is installed on a pole, they shall be placed on the same
side of the pole. Transformers installed on metal mounting brackets shall not
extend beyond the vertical plane through the centerline of the pole.
Exception:
Units installed on
non-climbable poles may extend beyond the vertical plane through the centerline
of the pole. (See Rule 22.6-D)