Rule 58.3-D4

 

58.3    D. Operating Mechanism

(4) Where line switches are operated from the ground level by means of all–metal control mechanisms without suitable insulating links or sections, an insulated platform shall be provided unless such operating mechanism is effectively grounded.

 

Strikeout and Underline Version

Rule 58.3-D4

 

58.3    D. Operating Mechanism

(4) Where line switches are operated from the ground level by means of all–metal control mechanisms without suitable insulating links or sections,:

(a) An insulated platform shall be provided unless such operating mechanism is, or

(b) The operating mechanism and non-insulated platform shall be bonded and effectively grounded.

 

Final Version

Rule 58.3-D4

 

58.3    D. Operating Mechanism

(4) Where line switches are operated from the ground level by means of all–metal control mechanisms without suitable insulating links or sections:

(a) An insulated platform shall be provided, or

(b) The operating mechanism and non-insulated platform shall be bonded and effectively grounded.