94.6   Electric IOUs’ Proposed Rule 94.6-C

 

          C. Unnecessary impairment of the climbing space or interference with fall restraint and fall protection equipment is not permitted by the application of Rule 54.7 or Rule 84.7.

 

          AT&T Mobility and CTIA’s Proposed Rule 94.6-C

 

          C. This Rule is not intended to authorize unnecessary interference with fall restraint and fall protection equipment. Examples of obstructions that shall not be considered to interfere with fall restraint and fall protection equipment include, but are not limited to, the following:

 

(1)        Surface-mounted equipment that occupies no more than 18 inches of vertical space;

 

(2)        Equipment stood off from the pole to maintain a minimum of 4 inches of clear space between the equipment and the pole;

 

(3)        Appropriately designed and installed surface-mounted risers;

 

(4)        Obstructions detailed in Rules 54.7-A2c(3) and 84.7-A(5).

 

SED’s Proposed Rule 94.6-C 

 

          C. Interference with fall restraint and fall protection equipment is not permitted by the application of Rule 54.7 or Rule 84.7.

 

Final Version

Rule 94.6-C

 

94.6   C. Antennas and all associated attachments shall not impair climbing space or interfere with fall restraint and fall protection equipment except as permitted by the application of Rule 54.7 or Rule 84.7.

 

Note: Examples of attachments that might not interfere with fall restraint and fall protection equipment include, but are not limited to, the following:

  

(1)        Surface-mounted equipment that occupies no more than 18 inches of vertical space.

 

(2)        Equipment stood off from the pole to maintain a minimum of 4 inches of clear space between the equipment and the pole.

 

(3)        Appropriately designed and installed surface-mounted risers.