Rule 80.1
80.1 Inspection
Requirements for Communication
Lines:
A. Patrol and
Detailed Inspections
[*
* * * ]
(2) Statewide Inspection
Requirements
Each company shall prepare,
follow, and modify
as necessary,
procedures for conducting patrol or
detailed
inspections for all
of its Communication Lines throughout
the
State. Consistent with Rule
31.2, the type,
frequency and thoroughness of
inspections shall
be based upon the
following factors:
• Fire threat
• Proximity to overhead power
line facilities
• Terrain
• Accessibility
• Location
Each company
that discovers a safety hazard on or near a communications facility or electric
facility involving another company while performing inspections of its own
facilities pursuant to this rule shall notify the other company and/or facility
owner of such safety hazard in accordance with Rule 18(B).
Strikeout and Underline Version
Rule 18
80.1 Inspection
Requirements for Communication
Lines:
A. Patrol and
Detailed Inspections
[*
* * * ]
(2) Statewide Inspection
Requirements
Each company shall prepare,
follow, and modify
as necessary,
procedures for conducting patrol or
detailed
inspections for all
of its Communication Lines throughout
the
State. Consistent with Rule
31.2, the type,
frequency and thoroughness of
inspections shall
be based upon the
following factors:
• Fire threat
• Proximity to overhead power
line facilities
• Terrain
• Accessibility
• Location
Final Version
Rule 18
80.1 Inspection
Requirements for Communication
Lines:
A. Patrol and
Detailed Inspections
[*
* * * ]
(2) Statewide Inspection
Requirements
Each company shall prepare,
follow, and modify
as necessary,
procedures for conducting patrol or
detailed
inspections for all
of its Communication
Lines throughout the State. Consistent with Rule 31.2,
the
type, frequency
and thoroughness of
inspections shall
be based upon the
following factors:
• Fire threat
• Proximity to overhead power
line facilities
• Terrain
• Accessibility
• Location
Each company that
discovers a safety hazard on or near a communications facility or
electric
facility involving another
company while performing
inspections of its own
facilities pursuant to this rule shall notify
the
other company and/or facility
owner
of such safety
hazard in accordance with
Rule 18‑A3.