Original Version
Rule 55.3-D
55.3-D. Additional Insulation
Insulators used in territories where fog or lighting conditions
prevail should be given more liberal factors of safety than those indicated
in Table 12.
Insulators used at crossings or conflicts shall conform to Rules 104 and
114.
Strikeout and Underline Version
Rule 55.3-D
55.3-D. Additional Insulation
Insulators used in territories where fog or lightning
conditions prevail should be given more liberal factors of safety than those
indicated in Table 12
In partial underground distribution, the primary transformer
bushings shall have ratings of not less than 95 kV BIL and a dry flashover
of not less than 60 kV; line conductor insulators, either post clamp or dead-end
type, shall have a dry flashover rating of not less than 80 kV.
Insulators used at crossings or conflicts shall conform to Rules 104 and
114."
Final Version
Rule 55.3-D
55.3-D. Additional Insulation
Insulators used in territories where fog or lightning
conditions prevail should be given more liberal factors of safety than those
indicated in Table 12.
In partial underground distribution, the primary transformer bushings shall
have ratings of not less than 95 kV BIL and a dry flashover of not less than
60 kV; line conductor insulators, either post clamp or dead-end type, shall
have a dry flashover rating of not less than 80 kV.
Insulators used at crossings or conflicts shall conform to Rules 104 and
114.