Original Version
Rule 54.4-H2
54.4-H2) Attached Conductors: Unprotected conductors
not exceeding 20,000 volts may be supported by attachments to buildings,
bridges and other structures. To conductors of 0-750 volts so supported,
the clearances of Table 1, case 7 columns B, C, and D shall apply.
To conductors of 750-20,000 volts so supported a minimum horizontal clearance
of 8 feet shall apply.
In lieu of theses requirements for unprotected conductors, supply conductors
may installed on the surface of buildings, bridges and other structures in
grounded metal conduit or other grounded sheath or grounded shield suitably
protected from mechanical injury.
Strikeout and Underline Version
Rule 54.4-H2
54.4-H2) Attached Conductors: Unprotected conductors
not exceeding 20,000 21,000 volts may be supported
by attachments to buildings, bridges and other structures. To conductors
of 0-750 volts so supported, the clearances of Table 1, case 7 columns B,
C, and D shall apply. To conductors of 750-20,000
21,000 volts so supported a minimum horizontal clearance of 8 feet shall
apply.
In lieu of theses requirements for unprotected conductors, supply conductors
may installed on the surface of buildings, bridges and other structures in
grounded metal conduit or other grounded sheath or grounded shield suitably
protected from mechanical injury.
Final Version
Rule 54.4-H2
54.4-H2) Attached Conductors: Unprotected conductors
not exceeding 21,000 volts may be supported by attachments to buildings,
bridges and other structures. To conductors of 0-750 volts so supported,
the clearances of Table 1, case 7 columns B, C, and D shall apply.
To conductors of 750-21,000 volts so supported a minimum horizontal clearance
of 8 feet shall apply.
In lieu of theses requirements for unprotected conductors, supply conductors
may installed on the surface of buildings, bridges and other structures in
grounded metal conduit or other grounded sheath or grounded shield suitably
protected from mechanical injury.