Original Version
Rule 54.9-E4
54.9-E4)    In Rural Districts: In rural districts (see
definition, Rule 21.0-B) where one circuit only of 7500-21,000 volts is supported
on the poles above conductors in rack construction, the vertical clearance
between the top conductor in rack construction and the nearest 7500-21,000
volt conductor level may be less than 6 feet but not less than 4 feet and
no guard arm is required.
  
  
Strikeout and Underline Version
Rule 54.9-E4
  
54.9-E4)    In Rural Districts: In rural districts
(see definition, Rule 21.0-B) where one circuit only of 7500-21,000
 22,500 volts is supported on the poles above conductors in rack construction,
the vertical clearance between the top conductor in rack construction and
the nearest 7500-21,000 22,500  volt conductor
level may be less than 6 feet but not less than 4 feet and no guard arm is
required.
    
    
    
Final Version
Rule 54.9-E4
    
54.9-E4)    In Rural Districts: In rural districts
(see definition, Rule 21.0-B) where one circuit only of 7500-22,500 volts
is supported on the poles above conductors in rack construction, the vertical
clearance between the top conductor in rack construction and the nearest
7500-22,500 volt conductor level may be less than 6 feet but not less than
4 feet and no guard arm is required.